Power supply |
24
2 VAC/DC
|
| Current
drain |
Standby:
8 mA, Active: 20 mA @24VDC
|
| HVAC
control |
Form
C relay, 30 VAC/DC, 0.2 A max.
|
| Light
control |
TTL
output, Standby: 0V, Active: 5V
|
ON
delay
|
0
- 10" - 30" - 1' - 5' - 10' selectable
|
| OFF
delay |
10"
- 1' - 5' - 10' - 20' - 30' selectable
|
| Photocell
sensor |
CdS
|
| Mounting
height |
2.4
~ 4.2 m
|
| RFI
immunity |
20
V/m average
|
| Humidity |
95%
RH max.
|
| Op.
temperature |
-10°C~60°C
(14°F~140°F)
|
| Dimensions |
110
(dia.) x 60 mm (H)
|
|
The
OS-362D is a ceiling mount duplex occupancy sensor for automatic operation
control of
HVAC and Lighting. This sensor provides 360 degree omni-directional occupancy
detection of individual rooms or open areas.
An innovative
dual delay processor makes this sensor smart enough to verify the nature
of occupancies.
In addition to the HVAC operation control, this duplex occupancy
sensor also provides signal for
instant light control. With one installation, the OS-362D can offer both
HVAC and lighting controls to maximize the benefits of occupancy-oriented
building energy management system.
|